1、Apply for temperature monitoring & controlling in duct (TTD2N), water and steam pipe(TTD4N), outside air(TTD3N), remote(TTD5N) and strap-on(TTD6N)
2、High performance digital temperature sensor and digital technology applied, ensure accurate measurement fast response and good long term stability
3、Multiple outputs selection, over voltage and reverse polarity protection, high reliability and anti-interference capability
4、Optional relay for alarm or ON/OFF control
5、Wide working temperature range and fast response
6、LCD & function keys can set parameters and calibrate output, so the product can become a stand alone controller
7、High protection rate up to IP65
Sensor: Digital temperature sensor
Range: see models
Output: 4~20mA (3 wires) &0~10VDC, RS485/Modbus
Output Load: ≤500Ω (current), ≥2KΩ (voltage)
Relay: 1×SPST, 3A/30VDC, 3A /250VAC
Accuracy: <±0.5°C@ -10~85°C, see accuracy curve
Power: 16~28VAC/16~35VDC
Work Temp.: -30~70°C (LCD: -20~70°C), 0~95%RH (Non cond.)
Storage Temperature: -30~70°C
Medium Temperature: -40~100°C (TTD2N, TTD4N)
Housing: ABS housing, SS probe (φ6mm), SS well
Cable (TTD5N): Black, silicone, 3*0.3mm², 1m length, -60~180°C, Rconductor=0.069Ω/m, Rinsulation >100MΩ (25°C)
Strap on (TTD6N): stainless steel, diameter 15~150mm
Protection: IP65(IP68 for TTD5N’s probe,1m water depth)
Weight: TTD2N:315g; TTD3N:195g; TTD4N:510g; TTD5N:345g; TTD6N:390g
Approval: CE
Optional Accuracy: 0.25°C@ -20 ~105°C
(Add “H” after part number)
Display and Keys: 4 digits LCD, with unit indication, backlight, 3 touch keys, see more details on LCD & Keys operation

Models

Note 1: Every product can be set ranges with accuracy ≤±0.5°C @-10~85°C by LCD & function keys; code 7 product can be set all ranges in -40~125°C with accuracy≤±0.5°C.
Note 2: Refer to working environment ambient guide GB/T4200 and WBGT, etc., the relay default settings are ON-30.0°C/OFF-29.5°C and can be customized or set by LCD & function keys.